| When atmospheric temperature is below than 22'C, the cooling test is omitted but air volume test |
| to be carried out according to above procedure, "4". |
| |
|
 |
Procedure |
| |
1. |
During the test, ensure that all windows and
doors are closed. |
| |
2. |
Open all door louvers and ventilators. |
| |
3. |
Keep all dampers in the set position adjusted
during the air volume test |
| |
4. |
Start air handling unit, refrigerating machinery
and all mechanical ventilation fans. |
| |
5. |
Keep all the system in operation until temp.
and humidity become steady condition |
| |
|
|
 |
Measuring and recording |
| |
1. |
Using record format (sheet 3), measure and record
the data of refrigerating machinery. |
| |
2. |
Using record format (sheet 4), measure and record
the data of air handling unit (AHU) |
| |
|
& package air conditioner (PAC) and environmental
condition. |
| |
3. |
Using record format (sheet 5), measure and record
room condition. |
| |
|
Measurement to be recorded 12 times at hourly
at on hour intervals respectively. |