Air volume test |
After completion of installation of equipments, pipings, duct work and electrical work for the HVAC | ||
system, air volume test to be carried out and the measurement of the test to be recorded on | ||
designated sheets. | ||
Procedure | ||
1. | Open all the air inlets and outlets of the HVAC system as well as natural vent. system. | |
2. | Open all the balancing dampers and fire dampers. | |
3. | Start all the fans for HVAC system. | |
4. | Adjust the mixing ratio of fresh air from outside and recirculation air with the balancing | |
damper of the air conditioning unit | ||
5. | Adjust the design air quantity with volume damper if provided for fans. | |
6. | Mark a set position on each damper. | |
Test and measuring devices | ||
"Anemomaster" or "Anemometer" may be used for measuring air velocity to get air flow quantity. | ||
Prepare a hopper made of galvanized steel sheet as below figure and cover diffuser or air | ||
terminal with it. |
Measure air velocity with putting the element of Anemometer just before the discharge side of | ||
hopper. With the measurement of air velocity, calculate actual air volume with above formula. | ||
Calculation of actual air volume with measured air velocity. | ||
V = 63.6 x v | ||
Here, | V = air volume (m2/h) | |
v = measured air velocity (m/sec) | ||
If designed air volume (air velocity) is not obtained, adjust control knob of the diffuser or air | ||
terminal, or volume damper concerned to the system. |
Measuring and recording | ||
For recording the measurements, use given formats. The sheets are attached to the end of | ||
this procedure. The result of measurement to be confirmed by Owner's representative and | ||
reported to the design office and concerned departments. | ||
1. | Using record format (sheet 1), record electrical data of every mechanical ventilation fan | |
for accommodation. | ||
2. | Using record format (sheet 2), record measured air velocity on the column and put in air | |
volume calculated with the air velocity respectively. |