| When atmospheric temperature is higher than
22'C, the heating test is omitted but air volume test |
| to be carried out according to above procedure,
4. |
| |
|
|
 |
Procedure |
| |
1. |
During the test, ensure that all windows and
doors are closed. |
| |
2. |
Open all door louvers and ventilators. |
| |
3. |
Keep all dampers in the set position adjusted
during the air volume test. |
| |
4. |
Start the air con. unit as well as all the mechanical
vent. fans and connect electric power |
| |
|
switch "ON". |
| |
5. |
Start steam generator inter-connected to humidistats
after charging fresh water to the |
| |
|
humidifying equipment. |
| |
|
|
 |
Measuring and recording |
| |
Using format(sheet 5), measure room temp. and
humidity. |