Heating test |
When atmospheric temperature is higher than 22'C, the heating test is omitted but air volume test | ||
to be carried out according to above procedure, 4. | ||
Procedure | ||
1. | During the test, ensure that all windows and doors are closed. | |
2. | Open all door louvers and ventilators. | |
3. | Keep all dampers in the set position adjusted during the air volume test. | |
4. | Start the air con. unit as well as all the mechanical vent. fans and connect electric power | |
switch "ON". | ||
5. | Start steam generator inter-connected to humidistats after charging fresh water to the | |
humidifying equipment. | ||
Measuring and recording | ||
Using format(sheet 5), measure room temp. and humidity. |