Heating test
When atmospheric temperature is higher than 22'C, the heating test is omitted but air volume test
to be carried out according to above procedure, 4.
     
Procedure
  1. During the test, ensure that all windows and doors are closed.
  2. Open all door louvers and ventilators.
  3. Keep all dampers in the set position adjusted during the air volume test.
  4. Start the air con. unit as well as all the mechanical vent. fans and connect electric power
    switch "ON".
  5. Start steam generator inter-connected to humidistats after charging fresh water to the
    humidifying equipment.
     
Measuring and recording
  Using format(sheet 5), measure room temp. and humidity.