After election of provision refrigeration plant onboard and finished refrigerant pipe work prior to application of insulation, pressure/leak test to be performed as follow procedure.

1. Close suction valve and discharge valve of compressor.
2. Open other valves installed on the refrigerant pipe line.
3. Low pressure switch to be isolated from suction line during this test and ensure that
expansion valves, pressure switches and etc. containing bellows or diagrams are
isolated from the rest of the plant during the test.
4. Charge N2 gas into entire system through charge valve until the pressure rises up to
the test pressure of 11§¸/§˛ G. for low pressure side.
( from expansion valve to compressor suction stop valve)
5. Close stop valve just ahead the expansion valve on the liquid line to separate high
pressure line from low pressure line.
6. Further charge dry N2 gas until the pressure rises up to the test pressure of 21§¸/§˛ G.
for high pressure side.
(From compressor discharge stop valve to manual stop valve installed just ahead
expansion valve)
7. Keep this condition for 12 hours and check the pressure drop at the end of this test.
The pressure drop should not exceed 0.35§¸/§˛ with following temp. correction.
P = Po - P (To/T) 0.35§¸/§˛
here, P = Pressure drop (§¸/§˛)
Po = Initial pressure (§¸/§˛)
To = Initial temperature (ĄŁK)
T = Temperature at end of test (ĄŁK)
8. In case of pressure drop exceeds 0.35 §¸/§˛, every joint to be checked by halide
torch detector or soap water. If leakage is detected, the test should be repeated
after the leak part repaired.
Pressure and leak test of refrigerant piping system.